- (104bs) Gas Detection Management in Petrochemical Plant
That period were 307 detectors installed in Olefins 1, Olefins 2, Aromatics 1, Aromatics 2 and tanks farm. These are compound of reliable system to detect small leakages around the industrial area and permit a quick response to the problem.
Bases of the project:
Gas Dispersion Study took into account:
The existing architecture of the 307 detectors allows a full scan of the operational area. Thus this means it can be made as to the events management process from the operator panel in the control room together with the field operator.
|
FLAMMABLE GAS DETECTOR - RANGE OF LEL (%) |
|||
|
Registration on shift log book |
Registration of causes on shift log book |
Registration fo deviation on sap with simple approach investigation |
Registration of deviation on sap with complete approach investigation |
|
≥ 5 % and < 20 % |
≥ 20 % and < 40 % |
≥ 40 % and < 80% |
> 80% |
The operator panel to verify that there is an alarm; it identifies the location of the detector alarmed and safest route to traverse the field operator to go check if there is any leakage at the site or any task that may have caused the alarm detector. This approach allows of detecting anomalies in the process early and taking corrective action in advance.
The record of nonconformities flammability according to table above allows us to understand the causes and track events with potential to larger leaks, minimizing the occurrence of events with consequences more relevant to the integrity of operating process area.