Eliminating Hydrogen Fire in CCR Units
The Oleflex catalyst regeneration system requires catalyst transfer from hydrogen/ hydrocarbon atmosphere in reactors to the oxygen rich atmosphere in the regenerator and back again. This requires the valves to be operated at a high cycle normally about 8 times an hour.
Due to this high operation cycle, the gland packing tends to become loose leading to minor passing. And due to presence of hydrogen, there are chances of fires.
It was identified that high rate of packing leaks was observed in the Fisher V-Ball and Metso ball valve. These are rotary valves while compared to other linear valves. Both the valves have conventional packing design with nut and bolt gland tensioning using gland followers and lock nut. This is the conventional style used in general purpose valve design.
It was observed that the valve started to leak from the gland even after one month of torque.
Also, the packing material used is laminate graphite. Better sealing will be provided by PTFE. The
limitation is temperature should be less than 230 Deg Operations have confirmed that the operating.
temperature is well below 200 Deg C. Therefore, a reliable alternative would be to replace the valve with an enviro seal package with PTFE material.